Búsqueda/compra
Fire Resistant Single Core 300-500V
|
Nominal Cross Section Area |
No./Nominal Diameter of Strands |
Nominal Insulation Thickness |
Nominal Sheath Thickness |
Without Earth Conductor |
|
mm² |
No./mm |
mm |
mm |
Nominal Overall Diameter |
Approx. Weight kg/km |
mm |
|||||
1.5 |
7/0.53 |
0.5 |
0.5 |
4.4 |
29 |
2.5 |
7/0.67 |
0.5 |
0.5 |
4.9 |
40 |
4 |
7/0.85 |
0.5 |
0.5 |
5.5 |
55 |
Description of Fire Resistant Single Core 300-500V
Rated voltage: 300/500V
Basic standard: BS 7211
Conductor: bare annealed copper wire, stranded wire to IEC(EN) 60228 class 2
Fire lyer: Mica glass tape
Insulation: PVC (XLPE)
Sheath: LSZH compound to BS 7655-6.1
Operating temperature range (fixed state): -30°C – +90°C
Operating temperature range (mobile state): -20°C – +50°C
Min bending radius: 6 time of Overall Diameter
Insulation resistance: 20 MΩ x km (at 20°C)
Short circuit temperature: 250°C
Circuit Integrity |
IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814(FE180); |
|
CEI 20-36/2-1; SS229-1; NBN C 30-004 (cat. F3); |
|
NF C32-070-2.3(CR1) |
Flame Retardance (Single Vertical Wire Test) |
EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; |
|
VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); |
|
CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires |
EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30- |
|
004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free |
IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; |
|
CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission |
IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; |
|
CEI 20-37/2-2 ; BS 6425-2* |
Minimum Smoke Emission |
IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; |
|
CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases |
NES 02-713; NF C 20-454 |
Application Of Fire Resistant Single Core 300-500V
The cables are designed for facilities where keeping and maintaining integrity of the electrical circuit is critical in power supply system.
The cables are widely used in underground tunnels, emergency lightings, fire alarm systems, control and power circuits, power stations, lifts, escalators, and high-rise buildings.
As a reliable electric cable factory, we can offer sorts of xlpe insulated cable for sale, if you are interested, please contact us.
Buen trato: comprar del vendedor
Esta página es acerca de los importadores y exportadores de Fire Resistant Single Core 300-500V Buscar en la categoria : Búsqueda/compra Buscar en la categoria : resistant, single, core, fire, 500v |
Domingo 02 septiembre 2007
LA CELLULETTE est la 1° sandale minceur avec tests d'efficacité effectués par un laboratoire Français agréé, prouvant un amincissement significatif en 28 jours d'utilisation. Une efficacité amincissante et anti capitons prouvée scientifiquement. Cette sandale présente une semelle...
Jueves 12 diciembre 2024
¡Hola Somos una empresa tradicional de mármol fosilizado (la SARL erfoud piedra), que se centra en los efectos geológicos de la región sur de Marruecos Erfoud. Nuestras actividades son variadas: la fabricación, todos los tipos de mármol fosilizado, particularmente marrón y negro...
Jueves 12 diciembre 2024
E teaching bulletin's good helper ! Four picture screens demonstrated what you need. The MX-1004PF/K Quad-View Video Processor is an advanced video processor for multimedia presentations. It is an ideal solution for applications where up to four video signals must be displayed on...