Informática
AKH-0.66 / K Split Core Current Transformer |
|
Type |
W |
H |
D |
a |
e |
Primary Input(A) |
Net Weight(kg) |
|
K-30×20 |
90 |
114 |
40 |
22 |
32 |
20-400 |
0.8-0.9 |
|
K-60×40 |
114 |
140 |
36 |
42 |
62 |
250-2000 |
1.0-2.0 |
|
K-80×40 |
122 |
162 |
40 |
42 |
82 |
300-3000 |
1.2-2.4 |
|
K-80×50 |
114 |
159 |
36 |
52 |
82 |
250-1000 |
1.1-1.4 |
|
K-80×80 |
144 |
159 |
36 |
82 |
82 |
250-1000 |
1.3-1.5 |
|
K-120×80 |
144 |
199 |
36 |
82 |
122 |
500-1500 |
1.5-2.3 |
|
K-120×60 |
164 |
214 |
52 |
62 |
122 |
400-5000 |
1.6-3.0 |
|
K-100×40 |
144 |
194 |
A |
42 |
102 |
1000-5000 |
1.6-3.2 |
|
K-130×40 |
144 |
224 |
52 |
42 |
132 |
1000-5000 |
1.6-3.6 |
|
K-140×60 |
164 |
234 |
52 |
62 |
142 |
1000-5000 |
1.7-3.7 |
|
K-160×80 |
184 |
254 |
52 |
82 |
162 |
1000-5000 |
2.8-3.7 |
|
K-200×80 |
184 |
294 |
52 |
82 |
202 |
1000-5000 |
3.5-4.5 |
|
Type |
Ratio(A) |
Class |
Burden(VA) |
|
K-30x20 |
20-75/1 |
1 |
0.2 |
|
100-150/5(1) |
1 |
1 |
|
|
200/5(1) |
1 |
1.5 |
|
|
250-300/5(1) |
0.5 |
1.5 |
|
|
350-400/5(1) |
0.5 |
2.5 |
|
|
K-60x40 |
250-300/5(1) |
1 |
1.5 |
|
350-400/5(1) |
0.5 |
1.5 |
|
|
500-800/5(1) |
0.5 |
2.5 |
|
|
1000-1250/5(1) |
0.5 |
5 |
|
|
1500-2000/5(1) |
0.5 |
10 |
|
|
K-80x40 |
350/5(1) |
1 |
1.5 |
|
350-450/5(1) |
0.5 |
2.5 |
|
|
500-800/5(1) |
0.5 |
5 |
|
|
1000-2000/5(1) |
0.5 |
10 |
|
|
2500-3000/5(1) |
0.2 |
10 |
|
|
K-80x50 |
250-300/5(1) |
1 |
1.5 |
|
400-450/5(1) |
0.5 |
1.5 |
|
|
500-800/5(1) |
0.5 |
2.5 |
|
|
1000/5(1) |
0.5 |
5 |
|
|
K-80x80 |
250-300/5(1) |
1 |
1.5 |
|
400-450/5(1) |
0.5 |
1.5 |
|
|
500-800/5(1) |
0.5 |
2.5 |
|
|
1000/5(1) |
0.5 |
5 |
|
|
K-100x40 |
1000-2000/5(1) |
0.5 |
10 |
|
2500-3000/5(1) |
0.2 |
10 |
|
|
4000-5000/5(1) |
0.2 |
15 |
|
|
K-120x60 |
400-450/5(1) |
0.5 |
2.5 |
|
500-800/5(1) |
0.5 |
5 |
|
|
1000-2000/5(1) |
0.5 |
10 |
|
|
2500-5000/5(1) |
0.2 |
10 |
|
|
K-120x80 |
500-800/5(1) |
0.5 |
2.5 |
|
1000-1200/5(1) |
0.5 |
5 |
|
|
1250-1500/5(1) |
0.5 |
7.5 |
|
|
K-130x40 |
1000-2000/5(1) |
0.5 |
10 |
|
2500-5000/5(1) |
0.2 |
10 |
|
|
K-130x60 |
1000-2000/5(1) |
0.5 |
10 |
|
2500-6000/5(1) |
0.2 |
15 |
|
|
K-140x60 |
1000-2000/5(1) |
0.5 |
10 |
|
2500-3000/5(1) |
0.2 |
10 |
|
|
4000-5000/5(1) |
0.2 |
15 |
|
|
K-160x80 |
1000-2000/5(1) |
0.5 |
10 |
|
2500-3000/5(1) |
0.2 |
10 |
|
|
4000-5000/5(1) |
0.2 |
15 |
|
|
K-200x80 |
1000-2000/5(1) |
0.5 |
10 |
|
2500-3000/5(1) |
0.2 |
10 |
|
|
4000-5000/5(1) |
0.2 |
15 |
|
|
K-Φ20 |
100A/20mA |
1 |
15Ω |
|
K-Φ30 |
200A/20mA |
0.5 |
10Ω |
|
K-Φ30 |
300A/20mA |
0.5 |
10Ω |
AKH-0.66/K Series Split Type Current Transformer Diagram
Hold the lower section firmly at the direction of arrow
Loosen two screws at the direction of arrow and remove them
Separate the lower section at the direction of arrow
Mount the copper bar and assemble the lower section at the direction of arrow
Hold it firmly at the direction of arrow
Hold the lower section firmly at the direction arrow, insert two screws and tighten nuts
Fix the copperbar with M5screwsand pressure plates
Acrel AKH-0.66/K Series SCT Current Transformers Uses
Our flexible split core current transformers are effectively used in reconstructing projects of urban
Split core current transformers are suitable for rural power grids to reconstruct
Split Core Current Transformer Installation
Press the arrow direction firmly to open the two screws and press the lower part
Unscrew and pull out the two screws in the direction of the arrow, see "P2"
Pull the screw and pull out the lower part in the direction of the arrow
After installing on the copper busbar, close the lower part in the direction of the arrow, see "P4"
Press firmly in the direction of the arrow
Press the lower part firmly and press the arrow direction to insert the two screws into the holes and tighten the screw width, see "P6"
Then use MS screws and pressure plate to install and press the steel row according to "P6"
Buen trato: comprar del vendedor
|
Esta página es acerca de los importadores y exportadores de AKH-0.66 / K Split Core Current Transformer Buscar en la categoria : Informática Buscar en la categoria : transformer, split, core, current |
Wednesday 14 September 2016
Cantidad : 5000 - Precio : 100,00 €
Bellows Seal Stop Valves (Angle Type) DIN Angle Type Bellows Sealed Stop Valve DIN Bellows Seal Globe Valve DIN Faltenbalgventil Eckform DIN Válvulas de fuelle(Paso angular.) DIN ventil uzavírací s vlnovcem rohový DIN Standard seteventil med belg (Vinkel modell) DIN Standardında...
Wednesday 04 November 2015
HDMI USB Extender over HDBaseT - CAT5e/6/7 Support Touch Screen [HDU700] is the unique and high-performance HDBaseT AV/PC Extender supporting HDMI, USB HID, high-quality S/PDIF Audio Line Out and IR at the best strengthened competitive price in the market. By using HDBaseT...
Wednesday 14 September 2016
Cantidad : 5000 - Precio : 50,00 €
Y Type Strainer DIN Standard Y Type Strainer DIN Y Schmutzfänger DIN Y Filtro tipo DIN Y filtr DIN Standard Y type filter DIN Standardında Y-Tipi Pislik Tutucu Lọc Y chuẩn DIN ETM Code No. : ETM FIG.T.830,ETM FIG.T.831 This ETM Y type strainer can be used in Industry, Power stations...